Many Valley households already run a generator through winter, and a floor heating zone is a perfectly ordinary load to put on one. A single 200 sq ft room at 15 W per sq ft is about 3 kW connected, and less than that on average once the thermostat is cycling.
So: one or two rooms on a household set, comfortably. The whole ground floor, no — not because it cannot be wired that way, but because the fuel cost of running 8 kW off a generator for hours is not something anyone does twice.
If outage resilience matters to you, this is a design decision to make at the survey, not afterwards: nominate the one or two zones that will run on generator supply and have them wired accordingly.